Automatic Pump Set
Features
- Loop or Day Tank Fuel Oil Transfer System
- Microprocessor-Based Monitoring and Control with Automatic Lead/Lag Function
- Automatic Pump Prime and Suction Line Integrity Check
- Main Storage Tank Monitoring
- Building Automation System (BAS) Interface
- Alarm and Event Summaries
The Automatic Fuel Oil Transfer Pump Set (ATPS) is a state of the art duplex pump sequencing and monitoring system. This system includes automatic lag pump back-up features that improve fuel system availability and safety. A pump set mounted LCD display is used to monitor day tank and pump set status and alarms.
Loop or Day Tank Fuel Oil Transfer System
- No. 2 or No. 4 Fuel Oil
- Flows from 20 to 2200 GPH
- Industrial type Cast Iron Internal Gear Pumps
Microprocessor-Based Monitoring and Control
- Large LCD Display
- Elapsed Time Recorders
- Main Storage Tank Gauge and Discriminating Leak Monitoring
Automatic Pump Prime and Suction Line Integrity Check
- Fuel transfer system suciton piping, pump prime and pump operation are automatically verified each week (adjustable)
- The lead and lag pump is automatically energized to prove the operation
- These tests are recorded in the controller memory with a time-date stamp for later verification
- If either lead or lag pump fails any of these test, the control system generates an audible and visual alarm and logs the "Failed Pump" condition
- To permit pump set testing, fuel oil piping system design must allow pump set discharge to return to the main storage tank
Automatic Lead/Lag
- Lead pump manual selection or automatic alternation on call for operation or run time hours
- Automatic lag pump back-up based on lead pump thermal overload, failure to produce flow, fuel demand exceeds capacity of the lead pump
- Automatic pump prime and suction line integrity check. Fuel transfer system suction piping, pump prime and pump operation are automatically verified each week (adjustable). Fuel system trouble can be identified and repaired before it is needed.
Main Storage Tank Monitoring
- Up to two tanks monitoring can be integrated into the Model ATPS Transfer Pump Set
- Accepts Model TG-EL-WF Wire Float, ultrasonic or differential pressure level sensors
- Overfill Alarm leak detector and level sensor test capability
Telephone Modem
- Allows the controller to dial out to an alphanumeric pager in response to alarms or events
- Allows a technician to dial in to the controller to vie all displays and make tuning adjustments
Building Automation Sytem (BAS) Interface
- BAS interface includes eight isolated relay contact output for "Pump 1 Fail", Pump 2 Fail", "Strainer High Differential", "Pump Set Leak", "Day Tank High", "Day Tank Low", and "Day Tank Leak" (all when applicable)
Alarm and Event Summaries
- Up to 200 alarms, system events and operator actions are listed in “first in first out” order with time/date stamp
Day Tank System
- Call for operation when Day Tank level falls below 50%, and continues to operate until the Day Tank level is greater than 80%
- Lead pump automatically alternates upon the next call for operation
- Upon detection low-level condition, the control system will automatically energize the backup pump, and both pumps will continue to operate until the level of oil reaches the high level point.
- Upon detection of loss of flow or pressure or lead pump thermal overload, the control system will automatically energize the backup pump and de-energize the lead pump

Loop System
- Lead pump is energized upon a call for operation, and run continuously until the demand is removed
- Lead pump automatically alternates upon the next call for operation
- The lead pump will automatically rotate every 1 to 168 hours (adjustable) or can be manually selected by the operator
- Upon detection of loss of flow or pressure or lead pump thermal overload, the control system will automatically energize the backup pump and de-energize the lead pump

Specifications
Motor Power: Control Circuit Power: Fluid: Pump: Motors: Strainer: |
120, 208, or 230 Vac 1 phase or 208, 230, or 460 Vac 3 phase 120 Vac 1 phase step down transformer included when selected motor voltage is other than 120 Vac No. 2 or No. 4 Fuel Oil is standard. Consult factory for other fuel types Bi-rotational, positive displacement type with cast iron housings and self-adjusting mechanical seals Base mounted, Open Drip-Proof (ODP) construction Simplex, ½", 1", 1½", or 2" (according to inlet line size) complete with 40 mesh basket |
Standard Equipment
- Microprocessor-based control with 16 line x 40 character
- LCD display and alarm/event and operator action log
- Control circuit transformer (if required)
- Alarm bell with alarm silence / reset pushbutton
- Two “Hand-Off-Auto” switches
- “Pump On” indicators
- Two magnetic motor starters with overload protection
- Two motor circuit breakers
- Two pump & motor assemblies
- Two relief valves, two check valves and four ball valves
- Two Simplex inlet strainers
- Inlet compound pressure gauge
- Pump discharge pressure gauges
- Three gauge isolation valves
- Pump Set Flow Proving Switch and Base assembly
Ordering Information
- Specify the pump set catalog number as follows:

* Pump Set sizes 101 through 103 are single phase only, sizes 104 through 206 are three phase only.
- Specify Loop or Day Tank Application
- Consult Factory for custom size
- Specify Tank Gauge Model TG-EL-D5. Up to two tanks, a Model TG-EL-D5-2 may be integrated into the Model ATPS Transfer Pump Set
- Specify any other application or monitoring requirements

Additional Ordering Information
| Optional Features | Catalog Number |
|---|---|
| Duplex Strainer in Lieu of two simplex strainers | add "-D" suffix |
| Duplex Strainer Differential Pressure Switch | add "-DP" suffix |
| Pump Set leak Detection Swtich | add "-L" suffix |
| Building Automation System (BAS) Discrete Output Contacts | add "-BAS" suffix |
| Telephone Modem | 190604 |