Day Tanks

Day Tank CombinationFeatures

[Technical Information]

Preferred Day Tanks provide a local supply of distillate or diesel fuel for boilers, emergency generators or other stationary engine driven or oil fired equipment.  Each Day Tank unit includes all necessary pipe connections, inspection port, manual fill port, and tank gauge, along with a variety of optional accessories.

Tank Specifcations

Mounting Base:

Metal Thickness:

Exterior Finish:

Manual Fill Port:

Inspection Port:

1" NPT Pipe Connections:

Vent Connections:


Approvals / Compliance:

Structural Steel Channel

10 gauge; All DT's and up to CDT-100,  7 gauge for CDT-160, 3/16" plate for CDT 220 & 275

Chemical resistant gray enamel over rust resistant primer

2" NPT

6" square gasketed plate

Tank Fill, Engine Fuel Return, Overflow to Storage Tank, Engine Fuel Supply, plugged Drain

Top Mounted
2"  --  20-60 Gallon
3"  --  80-190 Gallons
4"  --  220 Gallons and over

UL Approved, NFPA 30 compliant

Standard Equipment (DT & CDT)

  • “UL” Day tank assembly
  • “UL” Rupture basin assembly
  • Tank gauge (top mounted & float operated)
  • Three Drop tubes (one each for external device supply & return and day tank fill)
  • Containment – 160% of Day Tank capacity
  • Plugged drain tapping
  • Exterior chemical resistant finish (gray enamel over rust-resistant primer)
  • Structural steel channel mounting base

Rupture Basin Specifcations

Mounting Base:

Containment:

Leak Detector:

Metal Thickness:

Finish:

Drain:

Approvals/Compliance:

Structural Steel Channel

160% of tank capacity standard (other capacities available, consult factory)

Preferred RBS Float Switch

same as companion tank, Turned Edge Reinforcement

Chemical resistant gray enamel finish over rust resistant primer.

plugged 1" NPT coupling

UL Approved

Ordering Information

Ordering Table

Optional Features Catalog Number
50 PSI Test add "-EQ" suffix
NYC Certified add "-NY" suffix
Other Specs. add "-XX" suffix
Consult factory for other special requirements