Pump Set Leak Detector Switch


The Model PS-LDS Pump Set Leak Detection Switch detects leakage into the base plan of a pump set.



The Model PS-LDS Pump Set Leak Detection Switch can be installed anywhere there is a chance of having a fuel leak. This includes the base pan of a pump set, the rupture basin of a tank, or adjacent to a tank in a boiler or engine room. The switch installs easily into a mounting bracket (included) which welds to the side of the Pump Set base. The switch is activated by a magnetic float.
  • Detects Leakage In Base Pan Of A Pump Set
  • Easy Installation (Mounting Bracket Included)
  • Activated By Magnetic Float
The Model PS-LDS Pump Set Leak Detection Switch detects leakage into the base pan of a pump set. The switch installs easily into a mounting bracket which welds to the side of the pump set base. The switch is activated by a magnetic float.

Provide in the pump set containment base a leak sensor to shut off pumps and energize an audible and visual alarm should a leak occur. Switch shall be plasma welded stainless steel float-operated and fully contained within the pump set containment base pan for maximum protection from impact damage. Float shall be suitable for temperatures up to 250° F and pressures up to 300 PSIG. Pump Set leak detection shall be a Preferred Utilities Mfg. Corp., Danbury, CT, Model PS-LDS.