Thermopump
Features
- Loop or Day Tank Fuel Oil Transfer System
- Above ground storage tank supply & return oil line heating system
- Automatic Lead/Lag
The Thermopump system provides the above ground oil storage tank and exposed suction and return lines with a re-circulating flow of warm oil. Additionally, the Thermopump can provide automatic duplex pump sequencing and monitoring for Boiler and Day Tank applications.
Loop or Day Tank Fuel Oil Transfer System
- No. 2 Fuel Oil
- Flows from 20 to 2200 GPH
Above Ground Storage Tank Supply & Return Oil Line Heating System
- When heating is required an electric heater is powered on, also an automatic solenoid valve is energized to re-circulate fuel oil
- Redundant safety features that include an oil temperature switch and integral heater thermostat to protect against overheating, and guarantee that the oil returning to the tank will not be heated above 80°F
- Dual temperature sensors measure both the in line oil temperature, as well as the outdoor air temperature to activate the THERMOPUMP in response to climatic or internal tank conditions
Automatic Lead/Lag
- Lead pump manual selection or automatic alternation with automatic lag pump back-up, alarms and safety shutdown interlocks
Specifications
Power: Fluid: Pump: Motors: Strainer: |
Refer to table below No. 2 Fuel Oil is standard. Consult factory for other fuel types Bi-rotational, positive displacement type with cast iron housings and self-adjusting mechanical seals Base mounted, Open Drip-Proof (ODP) construction Duplex 1", or 1½" complete with 40 mesh perforated basket |
Standard Equipment
- Microprocessor-based control with message display and keypad
- Two magnetic motor starters with overload protection
- Two motor circuit breakers
- Control circuit transformer (if required)
- Alarm bell with alarm silence / reset pushbutton
- Two “Hand-Off-Auto” switches
- “Power On” indicator
- Two pump & motor assemblies
- Three relief valves, two check valves and four ball valves
- Duplex inlet strainer with DP switch / gauge
- Inlet compound pressure gauge
- Two discharge pressure gauges
- Three gauge isolation valves
- Flow switch and one base assembly leak detector switch
- Outdoor air temperature sensor
- Oil temperature switch
- Electric oil heater
- Integral heater thermostat
- Two temperature gauges
- Three-way motorized valve (optional)
Ordering Information
- Select Catalog Number below
- For non-standard or heavy oil pumping & heating systems, consult factory
| Volume vs. Heating Capacity | Specifications | ||||
|---|---|---|---|---|---|
| Catalog Number | Capacity | BTU | Motor HP | Heater K. Watt | Set Voltage |
| LO-101TP | 28.8 GPH | 5,000 | 1/3 | 1.5 | 115v-60hz-1Ø |
| LO-102TP | 48.0 GPH | 8,500 | 1/3 | 2.5 | 115v-60hz-1Ø |
| LO-103TP | 99.0 GPH | 17,000 | 1/3 | 5 | 230v-60hz-1Ø |
| LO-104TP | 180 GPH | 34,000 | 1/2 | 10 | 230v-60hz-3Ø |
| LO-105TP | 312 GPH | 61,000 | 1/2 | 18 | 230v-60hz-3Ø |
| LO-201TP | 384 GPH | 68,000 | 1/2 | 20 | 230v-60hz-3Ø |
| LO-203TP | 810 GPH | 143,000 | 3/4 | 42 | 230v-60hz-3Ø |
| LO-205TP | 1140 GPH | 205,000 | 1 1/2 | 60 | 460v-60hz-3Ø |
| LO-207TP | 2160 GPH | 368,000 | 2 | 108 | 460v-60hz-3Ø |